FPΣ Cautions for use
Restrictions when combining unit and using programming tools
Expansion I/O units for the FPΣ
- 1.The left-side expansion type FPΣ control unit is necessary for use with the FPΣ expansion I/O unit.
The previously available control units (Product number: FPG-C32T/FPG-C32TTM. Part number: AFPG2543/AFPG2543TM) cannot be used for expansion.
- 2.A maximum of four units can be used for expansion.
FPΣ and FP0 shared expansion I/O units and intelligence units
When combining expansion I/O units and intelligence units a maximum of up to three units can be added to the right side of control unit.
Programming tools
- 1.Either FPWIN GR Ver. 2 or FPWIN Pro Ver. 4 are necessary for use with the FPΣ control unit.
Users of FPWIN GR Ver. 1 will have to upgrade.
However, the upgrade only applies to Version 1.1 or higher. Those users with versions below Version 1.1 are asked to send us your user registration card. Upon receipt we will send you Version 1.1.
- 2.Either FPWIN GR Ver. 2.1 or FPWIN Pro Ver. 4.1 are necessary for use the left-side expansion type FPΣ control unit. An upgrade service
is available from software page
- 3.Handy-type programmers cannot be used with the FPΣ series PLC.
FP0 Power Supply Unit
Use is possible with the FPΣ Control Unit alone.
Unit's current consumption table
| Type of unit |
Control unit current consumption |
Expansion unit current consumption |
Input circuit current consumption |
Output circuit current consumption |
| This is the current consumed from the control unit power supply connector. If expan-sion units or intelligent units are added, the current is increased by the value indicated below. |
This is the current consumed from the expansion unit power supply connector. If a unit is not listed below, it means that it has no power supply connector |
This is the current consumed by the input circuits of the various units. This value indicates the current that flows into the input circuit. |
This is the current consumed by the output circuits of the various units. This value indicates the current used to drive the output circuits. This value does not include the load current value. |
| FPΣ control unit |
FPG-C32 FPG-C28 |
90 mA or less |
- |
77.2 mA or less |
70 mA or less |
| FPG-C24 |
160 mA or less |
- |
77.2 mA or less |
- |
| FPΣ expansion unit |
FPG-XY64D2T FPG-XY64D2P |
35 mA or less |
- |
112 mA or less |
15 mA or less |
| FPΣ intelligent unit |
FPG-PP11 FPG-PP12 |
50 mA or less |
20 mA or less |
- |
- |
| FPG-PP21 FPG-PP22 |
70 mA or less |
35 mA or less |
- |
- |
| FPG-EM1 |
35 mA or less |
- |
- |
- |
| FPG-CCLS |
40 mA or less |
40 mA or less |
- |
- |
| FPG-SL |
40 mA or less |
- |
- |
- |
| FP0 expansion unit |
FP0-E8X |
10 mA or less |
- |
34.4 mA or less |
- |
| FP0-E8R |
15 mA or less |
50 mA or less |
17.2 mA or less |
- |
| FP0-E8YR |
10 mA or less |
100 mA or less |
- |
- |
| FP0-E8YT/P |
15 mA or less |
- |
- |
24 mA or less |
| FP0-E16X |
20 mA or less |
- |
68.8 mA or less |
- |
| FP0-E16R |
20 mA or less |
100 mA or less |
34.4 mA or less |
- |
| FP0-E16T/P |
25 mA or less |
- |
34.4 mA or less |
24 mA or less |
| FP0-E16YT/P |
25 mA or less |
- |
- |
48 mA or less |
| FP0-E32T/P |
40 mA or less |
- |
68.8 mA or less |
48 mA or less |
| FP0 intelligent unit |
FP0-A21 |
20 mA or less |
100 mA or less |
- |
- |
| FP0-A80 |
20 mA or less |
60 mA or less |
- |
- |
| FP0-A04V |
20 mA or less |
100 mA or less |
- |
- |
| FP0-A04I |
20 mA or less |
130 mA or less |
- |
- |
| FP0-TC4 FP0-TC8 |
25 mA or less |
- |
- |
- |
| FP0-IOL |
30 mA or less |
40 mA or less |
- |
- |
| FP0-CCLS |
40 mA or less |
40 mA or less |
- |
- |
| Communication cassette |
FPG-COM1 FPG-COM2 |
20 mA or less |
- |
- |
- |
| FPG-COM3 FPG-COM4 |
25 mA or less |
- |
- |
- |